WARNING
Warranty Registration Card must be filled out by the customer and mailed within thirty (30) days of
installation in order to gain warranty coverage.
When receiving the PRESTIGE Excellence unit, any claims for damage or shortage in shipment must
be filed immediately against the transportation company by the consignee.
Leave all documentation received with appliance with owner for future reference.
* I N S T A L L A T I O N A N D M A I N T E N A N C E *
* I N S T A L L A T I O N A N D M A I N T E N A N C E *
2010-28 Manual Prestige Excellence
If the information in this manual is not followed exactly, a fire or explosion
may result causing property damage, personal injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas
suppliers instructions.
- If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or
the gas supplier.
prestige
Water Boiler
Excellence
Revised Date: 06/9/10
Part 1 of 2
NOTICE
Seitenansicht 0
1 2 3 4 5 6 ... 104 105

Inhaltsverzeichnis

Seite 1 - Excellence

WARNINGWarranty Registration Card must be filled out by the customer and mailed within thirty (30) days ofinstallation in order to gain warranty cover

Seite 2

Pre-Installation Items3SECTION I - Pre-Installation ItemsCode ComplianceThis product must be installed in accordance tothe following:- All applicable

Seite 3 - Table of Contents

19Water Heater MaintenanceMaintenance ScheduleAnnual service by qualified service technicianshould include the following:Any procedure required b

Seite 4

20If antifreeze is used in boiler water, check concen-tration. Boiler water (including additives) must bepractically non-toxic, having toxicity ra

Seite 5

21Replacement Parts321Fig. 7: Excellence Domestic Components

Seite 6

Water Heater SpecificationsSide View2.4" - 61 mm1/2” NPT Gas Connection37.2”945 mm8.0" 205 mm16" 406 mm1/2” NPSC Boiler Drain1” NPT Boi

Seite 7

Water Heater Specifications23Top View 3.4” 87 mm4.1” 105 mm8” 204 mm3/4” NPT DHW Inlet7.3" 186 mm3/4” NPSC Aux. Connection (Rear)1/2” NPSC Air

Seite 8 - Definitions

Additional quality water heating equipment available from: Triangle TubeTTP Brazed Plate Heat Exchangers- For domestic water, snow melting, radia

Seite 9

Pre-Installation ItemsRecommended ClearancesThe PRESTIGE Excellence is approved forzero clearance to combustibles, excludingvent and boiler

Seite 10 - Pre-Installation Items

Combustion Air and Venting5SECTION II - Combustion Air andVentingCombustion Air ContaminationIf the PRESTIGE Excellence combus-tion air inlet is

Seite 11

6Combustion Air and VentingVentilation and Combustion AirRequirements - Direct VentA Direct Vent appliance utilizes uncontaminat-ed outdoor air (piped

Seite 12 - Combustion Air and Venting

7Combustion Air and VentingMethods of Accessing Combustion Air Into ASpace - Category IVIndoor Combustion AirThe methods listed in this section

Seite 13

8Combustion Air and Venting- Not less than the sum of the areas of allvent connectors in the space.Two Permanent Openings Method. Two permanent open

Seite 14

Outdoor Opening(s) Location. Outdoor open-ing(s) shall be located in accordance with theOutdoor Combustion Air section.Outdoor Opening(s) Size. Ou

Seite 15

Removal of an Existing Boiler from aCommon Vent SystemWhen an existing boiler is removed from acommon venting system, the common vent-ing syste

Seite 16

11Combustion Air and VentingFor direct-vent appliances, mechanical-vent heating appliances or domestic hotwater equipment, where the bottom of

Seite 17

12Unit PreparationsSECTION III - Unit PreparationsHandling InstructionsThe PRESTIGE Excellence is generally easierto handle and maneuver once re

Seite 18

This manual outlines the requirements for installation of the PRESTIGE Excellence. Those require-ments include Boiler Piping, Venting/Combustion Air,

Seite 19 - Unit Preparations

13Unit PreparationsWall Bracket Installation - Solid Walls1. Locate the general area of the boiler place-ment.2. Place the wall-mounting bracket

Seite 20

Boiler PipingSECTION IV - Boiler PipingGeneral Piping Requirements- All plumbing must meet or exceed all local,state and national plumbing codes.- Su

Seite 21 - SECTION IV - Boiler Piping

Boiler Piping15CH Supply ConnectionCH Return Connection Pressure Relief Valve(Supplied with Boiler)3/4" Street ElbowAir VentDrain Piping Directe

Seite 22 - Boiler Piping

Boiler PipingAdditional Limit ControlIf a separate LWCO device is required by cer-tain local jurisdictions or when the boiler isinstalled above

Seite 23

The expansion tank must be located as shownin the piping diagrams on pages 19 through 21or as per recognized design methods. Refer tothe expansion

Seite 24

System Piping - Through BoilerIn applications in which primary/secondarypiping is not utilized and the system is zonedwith zone valves a circ

Seite 25

19Boiler Piping5546123333981011444444Zone Load Additional76Max.12" Zone Load 5 5 4 6 12 9 8 4 4 4 4 4 Zone Load Additional Max. 12" Zone L

Seite 26

20Boiler Piping744544512PZone Load AdditionalZone Load 6101141274986101141274SingleZone load 98Fig. 11: CH System Piping - Multiple Zone Valve with Si

Seite 27

21Boiler Piping5 5 4 6 12 9 8 4 4 Radiant Zone Additional 4 4 4 Radiant Zone Max. 12" 121011476Note: Manifold mounted valveactuators may be u

Seite 28

22Installation Vent/Combustion Air & CondensateSECTION V - Installing Vent /Combustion Air & Condensate DrainInstalling Vent and Combustion Ai

Seite 29 - SECTION V - Installing Vent /

PRODUCT AND SAFETY INFORMATIONDefinitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Produc

Seite 30

7. Continue the pipe from the drain assemblyto a floor drain or condensate pump.When selecting and installing a conden-sate pump, ensure the pump is

Seite 31 - SECTION VI - Gas Piping

SECTION VI - Gas PipingGas Supply Piping ConnectionThe gas supply piping must be installedin accordance to all applicable local,state and natio

Seite 32 - Gas Piping

NATURAL GASPipe Sizing - Natural GasRefer to Table 1 for Schedule 40 metallic pipelength and diameter requirements for naturalgas, based on ra

Seite 33

PROPANE GASPipe Sizing - Propane Gas1. Contact the local propane gas supplier forrecommended sizing of piping, tanks and100% lockup gas regulat

Seite 34

VenturiInlet SupplyPressure PortPropaneOrificeGas ValveGasketGas ValvePipe FittingGas ValveFig. 17: Gas Valve / Venturi AssemblyGas Piping27

Seite 35 - SECTION VII - Internal Wiring

SECTION VII - Internal WiringELECTRICAL SHOCK HAZARD. Foryour safety, disconnect electrical powersupply to the unit before servicing ormaki

Seite 36 - Internal Wiring

Fig. 20: PRESTIGE Excellence Boiler Factory WiringTo properly connect wires to terminal block, use wiring tool included with PRESTIGE. See wiring too

Seite 37 - SECTION VIII- External Wiring

SECTION VIII- External WiringInstallation ComplianceAll field wiring made during installation mustcomply with:- National Electrical Code NFPA 70 andan

Seite 38 - External Wiring

System Circulator - Zone Valve ApplicationTo energize the system circulator shown asitem 12 in Fig. 10 page 19 reference Fig. 21.Installer to

Seite 39

HNHigh Voltage120V. A . C .24V. A . C .RoomThermostatRoomThermostatZone 1Zone 2Additional zonesAdditional zones maybe added as shown aboveTo Prestige

Seite 40

Table of ContentsiiBackflow Preventer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Boiler System Piping Ap

Seite 41 - Start-Up Preparation

TTTo Prestige 24V Terminal StripCirculatorZone 1Thermostatzone 1HoneywellR845ARelay120HVA CNCirculatorZone 2Thermostatzone 2Additional zones may beadd

Seite 42 - Star-Up Preparation

SECTION IX - Start-Up PreparationCheck Boiler System Water ChemistryDo not use petroleum-base cleaning orsealing compounds in the boiler system.D

Seite 43

Use of Antifreeze in the Boiler SystemNEVER use automotive or ethylene gly-col antifreeze or undiluted antifreeze inthe primary system as freeze prote

Seite 44 - Start-Up Procedures

Check Low Water Cut-Off Device- The PRESTIGE Excellence is providedwith a factory installed LWCO device thatmeasures system pressure of more tha

Seite 45

SECTION X - Start-Up ProceduresFinal Checks Before Start-Upc Read page 42 through 45 regarding theoperation of the PRESTIGE Excellencecontro

Seite 46

Venting system must be sealed gas-tightto prevent flue gas spillage and potentialcarbon monoxide emissions, which willresult in severe personal in

Seite 47

FOR YOUR SAFETY READ BEFORE LIGHTINGOPERATING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE1. STOP! Read the safety information above. Thisappliance is

Seite 48

Set Boiler CH Target Temperature1. Press the MODE button until the displayshows PARA. This is the parameter modeof the control.2. Press the S

Seite 49 - StbY” is displayed

[3140] This is the normal CH operationcycle. After the flame is proven and stabi-lized the burner will fire at low input forapproximately 1

Seite 50

3. Lower the DHW storage temperature asoutlined in Set DHW Storage Temperatureto satisfy the call for heat.[1180] The post purge cycle begins. Th

Seite 51

iiiTable of ContentsSystem Circulator - Zone Valve Application . . . . . . . . . . . . . . . . . . . . . . . . 31External Modulating Control . . . . .

Seite 52

TO TEMPORARILY PLACE THE BURN-ER INTO LOW FIRE TEST MODE: pressthe MODE button until “StbY” is displayed.Then press and hold both the MODE and “-”b

Seite 53

Setting The Boiler ParametersParameter mode To access PARAMETER mode when the sys-tem is in STANDBY mode, press the MODEbutton once.To scroll throu

Seite 54 - Outdoor Reset Control

45Start-Up Procedures Display DigitSegmentsInformation Mode ItemsAccessing Boiler Information Information mode To switch from STANDBY mode to I

Seite 55

46Start-Up ProceduresError (Hard Lockout) ModeIf a system fault occurs while the boiler is run-ning, the system goes into lockout and the dis-play sta

Seite 56

SECTION XI - Outdoor Reset ControlThe boiler setpoint for a heating call can befixed or vary with the outdoor temperature. Ifthe application

Seite 57

48Outdoor Reset ControlSummer / Winter Switch at BoilerIf required the CH (Central Heating) system canbe turned off at the boiler, similar to

Seite 58 - External Modulating Control

49Outdoor Reset ControlCH Reset Curve Warmest Day(Parameter 12)This parameter is not applicable if an outdoorsensor is not connected to the boiler. W

Seite 59 - Factory Setting Parameters

9020601001401807064503010 0-1086Boiler Temperature ( F)Outdoor Air Temperature ( F)Parameter 4 Set PointParameter 10 Set PointParameter 12 SettingPara

Seite 60 - Check-Out Procedures

51External Modulating ControlSECTION XII - External ModulatingControlThe boiler can directly accept an analog 0-10VDC signal to control the firing r

Seite 61 - Installation Record

52External Modulating ControlFactory Setting Parameters

Seite 62 - Maintenance Schedule

SECTION XI - OUTDOOR RESET CONTROLMounting the Outdoor Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Wiring the Senso

Seite 63 - Procedures

SECTION XIII- Check-Out ProceduresPerform the following check-out proce-dures as outlined and check off items ascompleted. When procedures are

Seite 64 - Maintenance Procedures

SECTION XIV - Installation RecordPRESTIGE Excellence Model Number: Serial Number: Date of Installation: Fuel: Natural Gas

Seite 65

SECTION XV - Maintenance ScheduleService TechnicianAt least on an annual basis the following main-tenance should be performed by a qualified ser-vice

Seite 66

SECTION XVI - MaintenanceProceduresMaintenance ProceduresThe PRESTIGE Excellence should beinspected and serviced annually, prefer-ably at the st

Seite 67

Clean Condensate Drain Assembly1. Loosen the slip ring nut from the conden-sate drain assembly disconnecting theassembly from the boiler.2.

Seite 68

Check Expansion TankRefer to Section IV - Boiler Piping for rec-ommended location of the expansion tankand air eliminators.Closed -Type T

Seite 69

Check Control WiringInspect all control wiring. Ensure wiring is ingood condition and properly connected.Check Control Settings1. Set the control d

Seite 70

Check Flame SignalThe flame signal should be a min. 3μ Α −DC.Check the ignitor for fouling or damagedinsulation if a low flame signal is read.Check gr

Seite 71

The combustion chamber insulationcontains ceramic fibers, which are clas-sified as a possible human carcinogen.When exposed to extremely hi

Seite 72

510921B13 1A56 78Fig. 26: PRESTIGE Excellence Jacket ComponentsReplacement Parts62

Seite 73 - Product Specifications

Check Ventilation Air Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57Inspect Vent and Combustion Air Piping . . . . . . . . . . .

Seite 74

151311815101214932Fig. 27: PRESTIGE Excellence Internal ComponentsReplacement Parts63

Seite 75

Fig. 28: PRESTIGE Excellence Burner ComponentsReplacement Parts64

Seite 76

Fig. 29: PRESTIGE Excellence Electronic ComponentsReplacement Parts65

Seite 77

7.2" 183 mm 1/2” NPSC Boiler Drain 16" 405 mm18.9" - 479 mm 1/2” NPT Gas Connection 12" 305 mm1” NPT Boiler Return 1” NPT Boi

Seite 78 - Member of

2.4" - 61 mm1/2” NPT Gas Connection37.2”945 mm8.0" 205 mm16" 406 mm1/2” NPSC Boiler Drain1” NPT Boiler Supply1” NPT Boiler Return11.4&q

Seite 79 - Excellence

3.4” 87 mm4.1” 105 mm8” 204 mm3/4” NPT DHW Inlet7.3" 186 mm3/4” NPSC Aux. Connection (Rear)1/2” NPSC Air Vent Connection3/4” NPT DHW Outlet11

Seite 80 - Tables of Contents

FuelDOEHeating CapacityNote 1 & 4InputNote 4DOE SeasonalEfficiency AFUENote 3Net IBRRatingNote 299,000110,00095%ShippingWeightLbs / Kg190 / 86Natu

Seite 81

Note: Minimum allowable flow rate at full input: 5.0 gpm Graph 2: Pressure Drop Comparison Excellence 110 vs Grundfos UPS 15-58F-FCProduct Specificati

Seite 82

Additional Quality Water Heating Equipment Availablefrom Triangle Tube- Exclusive Tank-in-Tank design- Stainless steel construction- Available in 8 si

Seite 83 - HOT WATER CAN SCALD!

* I N S T A L L A T I O N A N D M A I N T E N A N C E * * I N S T A L L A T I O N A N D M A I N T E N A N C E * M A N U A LM A N

Seite 84 - Pre-Installation

Product & Safety Information1Indicates the presence of a hazardoussituation which, if ignored, will result indeath, serious injury or sub

Seite 85

Tables of ContentsProduct & Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Pre-Installation . . . . .

Seite 86

Tables of ContentsReplacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21Water Heater Specification

Seite 87 - Drain Valve

Product & Safety InformationIndicates the presence of a hazardous situ-ation which, if ignored, will result in death,serious injury or substant

Seite 88 - Check Valve

Product & Safety InformationBacteria can develop in the domestic watersystem if certain minimum water tempera-tures are not maintained.HOT WATER C

Seite 89

3Codes ComplianceInstallation of the Excellence Water Heater mustconform with the instructions in this manual andwhere applicable:• local

Seite 90

4Pre-InstallationLocating Water Heater• The Excellence is not intended for outdoorinstallations.• Locate Excellence so that any leakage from thet

Seite 91

5Installation - Domestic PipingTemperature & Pressure (T&P) Relief ValveTo reduce risk of excessive pressures and tem-peratures in the wate

Seite 92 - Water Heater Start-Up

6Installation - Domestic PipingDrain ValveDrain valve and fittings are supplied by others.Standard Installation• Install a tee connection at the domes

Seite 93

7Installation - Domestic PipingDomestic Piping• Union on domestic hot water outlet should bepiped at a higher elevation than domestic waterdrain valve

Seite 94

Installation - Domestic Piping8DHW Aux.ConnectionDHWCold WaterInletAir VentConnectionDHWHot WaterOutletT&P Valve(Drain Piping Not Shown)Fig. 2: S

Seite 95

2Do not use this appliance if any parthas been under water. Immediately calla qualified service technician to inspectthe appliance and to repla

Seite 96

9Cold Water Inlet 6 1 12" min. Heat Trap Loop (Optional) 12" Min. Heat Trap Loop (Optional) 5 4 9 8 3 M H C Installation - Piping Diagram

Seite 97

Installation - Piping Diagrams101. Mixing valve with check valve 2. Flow check valve3. Shut-off valve4. Backflow preventer or pressure reducing valve(

Seite 98

11Filling the Inner (Domestic Water) Tank• Never use the Excellence unless inner andouter tank of the water heater is completelyfilled with water.• I

Seite 99

12Water Heater Start-UpHOT WATER CAN SCALD!• Water temperatures over 125ºF can causesevere burns instantly, or death from scalds.• Feel water bef

Seite 100 - Water Heater Maintenance

13Water Heater Start-UpImportant Information - Read BeforeProceedingThis document is intended to be used by afactory trained and qualified

Seite 101

14Press STEP x5 - P_10Press STEP x6 - P_11Etc...After Parameter 4 the display will show P followedby a two-digit number that increases with

Seite 102 - Replacement Parts

Water Heater Start-Up15DHW Storage Temperature SettingThe parameter setting for the DHW storage tem-perature is Parameter 1 and is accessi

Seite 103 - Water Heater Specifications

Water Heater Start-Up16The DHW ON Differential setting of Parameter38 greatly affects the production of domestic hotwater. A minimum setting of Param

Seite 104 - Performances

Water Heater Start-Up174. Press the + or - button until the desired settingis achieved. Press STORE to save the setting.The display will flash when

Seite 105 - Triangle Tube

Water Heater Start-Up18FACTORy SETTING FOR PARAmETERS